Every MB records the values in the 16-bit device.<br />

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0<br />

Device<br />

16<br />

Device<br />

15<br />

Device<br />

14<br />

Device<br />

13<br />

Device<br />

12<br />

Device<br />

11<br />

Device<br />

10<br />

Device<br />

9<br />

Device<br />

8<br />

Device<br />

7<br />

Device<br />

6<br />

Device<br />

5<br />

Device<br />

4<br />

Device<br />

3<br />

Device<br />

2<br />

Device<br />

1<br />

MB#214: Monitored Status<br />

Explanations:<br />

Every MB records the status in the 16-bit device. 1 = normal; 0 = abnormal.<br />

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0<br />

Device<br />

16<br />

Device<br />

15<br />

Device<br />

14<br />

Device<br />

13<br />

Device<br />

12<br />

5.2 Monitor Word Registerss (MW)<br />

Device<br />

11<br />

Device<br />

10<br />

Device<br />

9<br />

Device<br />

8<br />

Device<br />

7<br />

Device<br />

6<br />

Device<br />

5<br />

Device<br />

4<br />

Device<br />

3<br />

Device<br />

2<br />

MW# Attribute Content Explanation Default Latched<br />

0 R/W<br />

1 R/W<br />

2 R/W<br />

3 ~ 32 R/W<br />

Number of devices<br />

monitored<br />

No. of station<br />

monitored<br />

Address of the<br />

device monitored<br />

No. of station<br />

monitored, address<br />

of the device<br />

monitored<br />

33 ~ 200 R/W Reserved<br />

201 ~ 216 R Monitored value<br />

216 ~ 300 R Reserved<br />

301 R Monitored status<br />

Cache mode normally enabled (b15=1),<br />

monitoring data in max. 16 slaves.<br />

0 Yes<br />

No. of the station to be monitored 0 Yes<br />

Recording the address of the device<br />

monitored<br />

Symbol “R” refers to read only; “R/W” refers to read and write.<br />

No. of the station to be monitore; recording<br />

the address of the device monitored.<br />

Every MW records the monitored value in 1<br />

register<br />

Every MW records the status in a 16-bit<br />

register. 1 = normal; 0 = abnormal<br />

0 Yes<br />

0 Yes<br />

0 No<br />

0 No<br />

Device<br />

1<br />

MW#0: Number of Devices Monitored<br />

Explanations:<br />

For setting up the number of devices to be monitored. Max. data in 16 slaves can be monitored.<br />

b15 is read only (Default =1: normally enabled cache mode)<br />

MW# (Odd Number): No. of Station Monitored<br />

Explanations:<br />

MW#1, MW#3, MW#5…MW#33 are for setting up the station No. (0 ~ 255) to be monitored.<br />

MW# (Even Number): Address of Device Monitored<br />

Explanations:<br />

MW32, MW34, MW#36…MW#34 are for setting up the address of the device to be monitored.<br />

14<br />

DVP-PLC Application Manual