2. Programming Concepts<br />

5. The analog output signals and their correspondi<br />

ng digital values:<br />

Mode<br />

Model<br />

20<strong>EX2</strong>/<strong>SX2</strong><br />

30<strong>EX2</strong><br />

Voltage -10 V~+10 V -2000~+2000 -32000~+32000<br />

Current<br />

+0 mA~+20 mA + 0~+4000 +0~+32000<br />

+4 mA~+20 mA + 0~+4000 +0~+32000<br />

6. The descriptions of the special data registers for the analog functions:<br />

Device<br />

D1062<br />

Function<br />

Average number of times analog input signals are input through CH0~CH3 of<br />

20<strong>EX2</strong>/<strong>SX2</strong>: 1~20, Default = K2<br />

Average number of times analog input signals are input through CH0~CH2 of<br />

30<strong>EX2</strong>: 1~15, Default = K2<br />

D1110 Average value of <strong>EX2</strong>/<strong>SX2</strong> analog input channel 0 (AD 0)<br />

D1111 Average value of <strong>EX2</strong>/<strong>SX2</strong> analog input channel 1 (AD 1)<br />

D1112 Average value of <strong>EX2</strong>/<strong>SX2</strong> analog input c hannel 2 (AD 2)<br />

Average value of 20<strong>EX2</strong>/<strong>SX2</strong> analog input channel 3 (AD 3)<br />

If D1062 is ON, the average value is the current value.<br />

D1113<br />

Displaying the status of the analog input channel of 30<strong>EX2</strong><br />

Please see the explanation below for more information.<br />

Enable/disable 20<strong>EX2</strong>/<strong>SX2</strong> AD channels<br />

(0: enable (default) / 1: disable)<br />

D1114 bit0~bit3 sets AD0~AD3.<br />

30<strong>EX2</strong> does not support this function.<br />

D1116<br />

D1117<br />

D1118<br />

Output value of analog output channel 0 (DA 0) of <strong>EX2</strong>/<strong>SX2</strong><br />

Output value of analog output channel 1 (DA 1) of 20<strong>EX2</strong>/<strong>SX2</strong><br />

30<strong>EX2</strong> does not support this function.<br />

For <strong>EX2</strong>/<strong>SX2</strong> series, sampling time of analog/digital conversion. Sampling<br />

time will be regarded as 2ms If D1118≦2.<br />

The description of D1113 for 30<strong>EX2</strong>:<br />

Bit15~12 Bit11~8 Bit7~4 Bit3~0<br />

Status of the analog Status of the analog<br />

Status of the analog<br />

Reserved<br />

input channel (AD2) input channel (AD1) input channel (AD0)<br />

The status of the analog input channel of 30<strong>EX2</strong>:<br />

Status 0x0 0x1 0x2<br />

Description Normal<br />

The analog input exceeds the The temperature sensor is<br />

upper/lower limit.<br />

disconnected.<br />

The upper/lowe r limit values for the analog input mode of 30<strong>EX2</strong>:<br />

Analog input mode Upper limit value Lower limit value<br />

-10~+10 V<br />

Voltage -5V~+5 V<br />

+32384 -32384<br />

+1 V ~+5 V +32384 -384<br />

2-67