2. Programming Concepts<br />

DABSR:<br />

1. M1029= ON when instruction is completed.<br />

2. When the instruction is re-executed for the next time, M1029 will turn off first then ON again<br />

when the instruction is completed<br />

ZRN, DRVI, DRVA:<br />

1. M1029 will be “ON” after Y0 and Y1 pulse output is completed. M1102 will be “ON” after Y2<br />

and Y3 pulse output is compeleted.<br />

2. When the instruction is re-executed for the next time, M1029 / M1102 will turn off first then<br />

ON again when the instruction is completed.<br />

Function Group<br />

Number<br />

Contents:<br />

Clear Instruction<br />

M1031, M1032<br />

M1031 (clear non-latched memory) , M1032 (clear latched memory)<br />

Device<br />

M1031<br />

Clear non-latched area<br />

M1032<br />

Clear latched area<br />

Devices will be cleared<br />

Contact status of Y, general-purpose M and general-purpose S<br />

• General-purpose contact and timing coil of T<br />

• General-purpose contact, counting coil reset coil of C<br />

• General-purpose present value register of D<br />

• General-purpose present value register of T<br />

• General-purpose present value register of C<br />

Contact status of M and S for latched<br />

• Contact and timing coil of accumulative timer T<br />

• Contact and timing coil of high-speed counter C for latched<br />

• Present value register of D for latched<br />

• Present value register of accumulative timer T<br />

• Present value register of high-speed counter C for latched<br />

Function Group<br />

Number<br />

Contents:<br />

Output State Latched in STOP mode<br />

M1033<br />

When M1033 = ON, PLC outputs will be latched when PLC is switched from RUN to STOP.<br />

Function Group<br />

Number<br />

Contents:<br />

Disabling all Y outputs<br />

M1034<br />

When M1034 = ON, all outputs will turn off.<br />