17.03.2014 Views

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

Function Group<br />

Number<br />

Communication Error Code<br />

M1025, D1025<br />

Contents:<br />

In the connection between PLC and PC/HMI, M1025 will be ON when PLC receives illegal<br />

communication request during the data transmission process. The error code will be stored in<br />

D1025.<br />

01: illegal instruction code<br />

02: illegal device address.<br />

03: requested data exceeds the range.<br />

07: checksum error<br />

Function Group<br />

Number<br />

Contents:<br />

Pulse output Mark and Mask function<br />

M1108, M1110, M1156, M1158, M1538, M1540, D1026, D1027, D1135, D1136,<br />

D1232, D1233, D1234, D1235, D1348, D1349<br />

Please refer to explanations of API 59 PLSR / API 158 DDRVI / API 197 DCLLM instructions.<br />

Function Group<br />

Number<br />

Execution Completed Flag<br />

M1029, M1030, M1102, M1103<br />

Contents:<br />

Execution Completed Flag:<br />

MTR, HKY, DSW, SEGL, PR:<br />

M1029 = ON for a scan cycle whenever the above instructions complete the execution.<br />

PLSY, PLSR:<br />

1. M1029 = ON when Y0 pulse output completes.<br />

2. M1030 = ON when Y1 pulse output completes<br />

3. M1102 = ON when Y2 pulse output completes.<br />

4. M1103 = ON when Y3 pulse output completes.<br />

5. When PLSY, PLSR instruction are OFF, M1029, M1030, M1102, M1103 will be OFF as well.<br />

When pulse output instructions executes again, M1029, M1030, M1102, M1103 will be OFF<br />

and turn ON when execution completes.<br />

6. Users have to clear M1029 and M1030 manually.<br />

INCD:<br />

M1029 will be “ON” for a scan period when the assigned groups of data comparison is completed<br />

RAMP, SORT:<br />

1. M1029= ON when instruction is completed. M1029 must be cleared by user manually.<br />

2. If this instruction is OFF, M1029 will be OFF.<br />

2-60