2. Programming Concepts<br />

Function Group<br />

Number<br />

Contents:<br />

Adjustment on Input Terminal Response Time<br />

D1020<br />

1. D1020 can be used for setting up the response time of receiving pulses at X0 ~X7 for <strong>ES2</strong><br />

series MPU. Default: 10ms, 0~20ms adjustable.<br />

2. When the power of PLC goes from “OFF” to “ON”, the content of D1020 is set to 10<br />

automatically.<br />

Terminal<br />

X0<br />

X7<br />

response time<br />

0ms<br />

1ms<br />

10ms<br />

15ms<br />

0<br />

1<br />

Set by D1020<br />

(default: 10)<br />

Update input<br />

10<br />

status<br />

15<br />

Status<br />

memory<br />

3. If the following programs are executed, the response time of X0 ~ X7 will be set to 0ms.<br />

However, the fastest response time of input terminals will be 50μs due to that all terminals are<br />

connected with RC filters..<br />

M1000<br />

MOV K0 D1020<br />

normally ON contact<br />

4. It is not necessary to adjust response time when using high-speed counters or interrupts<br />

5. Using API 51 REFF instruction has the same effect as modifying D1020.<br />

Function Group<br />

Number<br />

Contents:<br />

X6 pulse width detecting function<br />

M1083,M1084, D1023<br />

When M1084 = ON, X6 pulse width detecting function is enabled and the detected pulse width is<br />

stored in D1023 (unit: 0.1ms)<br />

M1083 On:detecting width of negative half cycle (OFFON)<br />

M1083 Off:detecting width of positive half cycle (ONOFF)<br />