2. Programming Concepts<br />

2. D1008 saves the STEP address where the timeout occurred<br />

Function Group Scan Time Monitor<br />

Number<br />

D1010~D1012<br />

Contents:<br />

The present value, minimum value and maximum value of scan time are stored in D1010 ~ D1012.<br />

D1010: current scan time<br />

D1011: minimum scan time<br />

D1012: maximum scan time<br />

Function Group<br />

Number<br />

Internal Clock Pulse<br />

M1011~M1014<br />

Contents:<br />

1. PLC provides four different clock pulses to aid the application. When PLC is power-on, the<br />

four clock pulses will start automatically.<br />

10 ms<br />

M1011 (10 ms)<br />

100 Hz<br />

100 ms<br />

M1012 (100 ms)<br />

10 Hz<br />

1 sec<br />

M1013 (1 sec)<br />

1 Hz<br />

1 min<br />

M1014 (60 sec)<br />

2. Clock pulse works even when PLC stops, i.e. activation of clock pulse is not synchronized<br />

with PLC RUN execution.<br />

Function Group<br />

Number<br />

Contents:<br />

High-speed Timer<br />

M1015, D1015<br />

1. When M1015 = ON, high-speed timer D1015 will be activated when the current scan<br />

proceeds to END instruction. The minimum resolution of D1015 is 100us.<br />

2. The range of D1015 is 0~32,767. When it counts to 32,767, it will start from 0 again.<br />

3. When M1015 = OFF, D1015 will stop timing immediately.<br />

Example:<br />

1. When X10 = ON, M1015 = ON to start high-speed timer and record the present value in<br />

D1015.<br />

2. When X10 = OFF, M1015 = OFF. High-speed timer is disabled.<br />

2-57