2. Programming Concepts<br />

2.16 Applications of Special M Relays and D Registers<br />

Function Group<br />

Number<br />

PLC <strong>Operation</strong> Flag<br />

M1000~M1003<br />

Contents:<br />

These relays provide information of PLC operation in RUN status.<br />

M1000:<br />

NO contact for monitoring PLC status. M1000 remains “ON” when PLC is running.<br />

M1000<br />

Y0 PLC is running<br />

Normally ON contact<br />

in PLC RUN status<br />

Keeps being ON<br />

M1001:<br />

NC contact for monitoring PLC status. M1001 remains “OFF” when PLC is running.<br />

M1002:<br />

Enables single positive pulse for the first scan when PLC RUN is activated. Used to initialize<br />

registers, ouptuts, or counters when RUN is executed..<br />

M1003:<br />

Enables single negative pulse for the first scan when PLC RUN is activated. Used to initialize<br />

registers, ouptuts, or counters when RUN is executed.<br />

PLC RUN<br />

M1000<br />

M1001<br />

M1002<br />

M1003<br />

scan time<br />

Function Group<br />

Number<br />

Monitor Timer<br />

D1000<br />

Contents:<br />

1. Monitor timer is used for moitoring PLC scan time. When the scan time exceeds the set value<br />

(SV) in the monitor timer, the red ERROR LED will be ON and all outputs will be “OFF”.<br />

2-55