2. Programming Concepts<br />

X20<br />

X21<br />

A-phase X0<br />

B-phase X1<br />

C251 present value<br />

3<br />

0<br />

1<br />

2<br />

5<br />

4<br />

3<br />

Counting up<br />

6<br />

5<br />

4<br />

3<br />

Counting down<br />

2<br />

1<br />

0<br />

Y0, C251 contact<br />

2.13 Special Data Register<br />

The types and functions of special registers (special D) are listed in the table below. Care should<br />

be taken that some registers of the same No. may bear different meanings in different series MPUs.<br />

Special M and special D marked with “*” will be further illustrated in 2.13. Columns marked with “R”<br />

refers to “read only”, “R/W” refers to “read and write”, “-“ refers to the status remains unchanged<br />

and “#” refers to that system will set it up according to the status of the PLC. For detailed<br />

explanation please also refer to 2.13 in this chapter.<br />

Special<br />

D<br />

Content<br />

<strong>ES2</strong> SS<br />

<strong>EX2</strong> 2<br />

SA<br />

2<br />

SX<br />

2<br />

OFF<br />

<br />

ON<br />

STOP<br />

<br />

RUN<br />

RUN<br />

Attrib. Latch Default<br />

-ed<br />

STOP<br />

D1000* SV of program scan ning WDT (Unit: 1ms) ○ ○ ○ ○ 200 - - R/W NO 200<br />

Displaying the firmware version of <strong>DVP</strong>-PLC<br />

D1001 ○ ○ ○ ○ - - - R NO #<br />

(initial factory setting)<br />

D1002* Program capacity ○ ○ ○ ○ - - - R NO #<br />

Sum of program memory (sum of the PLC internal<br />

D1003 ○ ○ ○ ○ # - - R YES 15872<br />

program memory.<br />

D1004* Syntax check error code ○ ○ ○ ○ 0 0 - R NO 0<br />

D1008* Step address when WDT is ON ○ ○ ○ ○ 0 - - R NO 0<br />

D1009 Number of LV (Low voltage) signal occurrence ○ ○ ○ ○ - - - R YES 0<br />

D1010* Current scan time (Unit: 0.1ms) ○ ○ ○ ○ # # # R NO 0<br />

D1011* Minimum scan time (Unit: 0.1ms) ○ ○ ○ ○ # # # R NO 0<br />

D1012* Maximum scan time (Unit: 0.1ms) ○ ○ ○ ○ # # # R NO 0<br />

D1015*<br />

Value of accumulative high-speed timer<br />

(0~32,767, unit: 0.1ms)<br />

○ ○ ○ ○ 0 - - R/W NO 0<br />

D1018* πPI (Low byte)<br />

○ ○ ○ ○<br />

H’ H’ H’<br />

H’<br />

R/W NO<br />

0FDB 0FDB 0FDB<br />

0FDB<br />

D1019* πPI(High byte)<br />

○ ○ ○ ○<br />

H’ H’ H’<br />

H’<br />

R/W NO<br />

4049 4049 4049<br />

4049<br />

D1020* X0~X7 input filter (unit: ms) 0~20ms adjustable ○ ○ ○ ○ 10 - - R/W NO 10<br />

Counting mode selection (Double frequency/ 4<br />

D1022 times frequency) for AB phase counter (From X0, ○ ○ ○ ○<br />

X1 input)<br />

4 - - R/W NO 4<br />