<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

Code Indication How to correct<br />

E8<br />

The node IDs of master and<br />

slave repeat.<br />

‣ Code display in D9980 as <strong>DVP</strong>-<strong>ES2</strong>-C is in master mode:<br />

Set the node ID of master and slave again<br />

and ensure their node IDs are sole.<br />

Code Indication How to correct<br />

F1<br />

F2<br />

Slave has not been added to<br />

node list of CANopen Builder<br />

software<br />

The data are being downloaded<br />

to <strong>DVP</strong>-<strong>ES2</strong>-C<br />

Add slave into the node list and then<br />

re-download the configured data.<br />

Wait to finish downloading the configured<br />

data.<br />

F3 <strong>DVP</strong>-<strong>ES2</strong>-C is in error status Re-download parameter configuration<br />

F4<br />

F5<br />

F8<br />

FB<br />

FC<br />

Bus-off is detected.<br />

<strong>DVP</strong>-<strong>ES2</strong>-C setting error such<br />

as incorrect node address<br />

Internal error; the error is<br />

detected in the internal memory<br />

The sending buffer in<br />

<strong>DVP</strong>-<strong>ES2</strong>-C is full.<br />

The receiving buffer in<br />

<strong>DVP</strong>-<strong>ES2</strong>-C is full.<br />

Check if CANopen bus cables are properly<br />

connected and ensure that all the node<br />

devices run at the same baud rate before<br />

re-powering.<br />

The node address of <strong>DVP</strong>-<strong>ES2</strong>-C should be<br />

set in the range: 1~127.<br />

After re-powering, change into a new one if<br />

the error still exists.<br />

Check if the CANopen bus cable is properly<br />

connected and then re-power.<br />

Check if the CANopen bus cable is properly<br />

connected and then re-power.<br />

‣ Code display in D9980 as <strong>DVP</strong>32<strong>ES2</strong>-C is in slave mode:<br />

Code Indication How to correct<br />

A0 <strong>DVP</strong>-<strong>ES2</strong>-C is being initialized. --<br />

A1<br />

A3<br />

B0<br />

B1<br />

<strong>DVP</strong>-<strong>ES2</strong>-C is pre-operational.<br />

The data are being downloaded<br />

to <strong>DVP</strong>-<strong>ES2</strong>-C<br />

Heartbeat message is timed-out<br />

PDO data length returned from<br />

the slave is not consistent with<br />

the length set in the node list.<br />

Check if the CANopen bus cable is properly<br />

connected<br />

Wait to finish downloading the configured<br />

data.<br />

Check if the CANopen bus cable is properly<br />

connected.<br />

Reset the PDO data length in the slave and<br />

download the new setting to <strong>DVP</strong>COPM-SL.<br />

7-26