<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

LED indicator Description How to deal with<br />

The red light<br />

flashes.<br />

The red light<br />

keeps on.<br />

There are syntax<br />

error existing in the<br />

program written to<br />

PLC or the PLC<br />

device or instruction<br />

is out of the allowed<br />

range.<br />

PLC scan is<br />

timed-out<br />

Judge the error cause according to the content<br />

value of the special register D1004 in PLC; find<br />

the program error position according to the<br />

content value of D1137. For more details on the<br />

error codes in D1004, please refer to “<strong>ES2</strong> series<br />

PLC operation manual (Programming)”.<br />

Reduce the time for executing PLC program or<br />

use WTD instruction<br />

‣ COM3(CANopen)Indicator<br />

LED indicator Description How to deal with<br />

The green<br />

light keeps on.<br />

The green<br />

light is in<br />

single flash.<br />

The green<br />

light flashes.<br />

The red light<br />

is in double<br />

flashes.<br />

The red light<br />

in single flash.<br />

The red light<br />

keeps on.<br />

<strong>DVP</strong>-<strong>ES2</strong>-C is<br />

normal.<br />

<strong>DVP</strong>-<strong>ES2</strong>-C stops.<br />

As <strong>DVP</strong>-<strong>ES2</strong>-C is in<br />

slave mode, it is<br />

preoperational;<br />

As <strong>DVP</strong>-<strong>ES2</strong>-C is in<br />

master mode, some<br />

slave is offline.<br />

The slave is off-line.<br />

At least one error<br />

counter in the CAN<br />

controller reaches or<br />

exceeds the warning<br />

level.<br />

Bus-off<br />

No resolution is required<br />

The superior equipment is downloading the<br />

network configuration and waiting to complete<br />

downloading.<br />

1. Check whether the wiring of the CANopen bus<br />

cable is correct.<br />

2. Check whether the baud rate of the master is<br />

the same as that of the slave.<br />

3. Check if the configured slaves have connected<br />

to the network.<br />

4. Check if any slave is offline.<br />

1. Check whether the CANopen bus cable is a<br />

standard one.<br />

2. Check whether both ends of the CANopen bus<br />

are connected to the terminal resistors.<br />

1. Check whether the CANopen bus cable is a<br />

standard one.<br />

2. Check whether both ends of the CANopen bus<br />

are connected to the terminal resistors.<br />

3. Check whether there is much interference<br />

around the CANopen bus cable.<br />

1. Check whether the wiring of the bus cable in<br />

the CANopen network is correct.<br />

2. Check whether the baud rate of the master is<br />

the same as that of the slave.<br />

7.5.2 CANopen Network Node State Display<br />

‣ While the special auxiliary relay M1349 of <strong>DVP</strong>-<strong>ES2</strong>-C is ON, the CANopen function is<br />

enabled and D9980~D9998 will be used as the special registers as the table shows below.<br />

Special register<br />

D9980<br />

D9981~D9996<br />

D9998<br />

Function<br />

Used for displaying the state of <strong>DVP</strong>-<strong>ES2</strong>-C.<br />

Used for displaying the state of 16 nodes in the network<br />

Used for monitoring the state of the entire CANopen network<br />

‣ As a master, <strong>DVP</strong>-<strong>ES2</strong>-C supports maximum 16 slaves ranging from node 1 to node 16.<br />