7 CANopen Function and <strong>Operation</strong><br />

When M0=ON, <strong>DVP</strong>-<strong>ES2</strong>-C sends out the first request message and D6000 should be<br />

101(hex) after the response message is transmitted back successfully. In program, if the<br />

value of D6000 is judged as 101(hex), the ReqID is changed into 2 and D6250 is given a new<br />

value 201(hex) and <strong>DVP</strong>-<strong>ES2</strong>-C sends out the request message again. By dong so, the<br />

real-time reading can be realized. After reading succeeds, the data returning from the target<br />

device are stored in D6000~D6005. The value of D6005: 100(hex)is the read value of P0-09.<br />

‣ Explanation of Response Message Devices:<br />

PLC device<br />

Content<br />

Explanation<br />

(Hex) High byte(Hex) Low byte(Hex)<br />

SDO<br />

response<br />

message<br />

mapping<br />

area<br />

D6000 0101 ResID = 01 Status code = 01<br />

D6001 0008 Reserved Size = 08<br />

D6002 4302 Type = 43 Node ID = 02<br />

D6003 2009 Main index high byte = 20 Index low byte = 09<br />

D6004 0004 Reserved Subindex = 00<br />

D6005 0100 Datum 1= 01 Datum 0= 00<br />

D6006 0100 Datum 3= 00 Datum 2= 00<br />

7.5 Indicators and Troubleshooting<br />

There are 6 LED indicators on <strong>DVP</strong>-<strong>ES2</strong>-C. Power indicator shows whether the power is normal,<br />

RUN and ERROR indicator display the state of running of internal program and COM3 displays the<br />

communication state of CANopen.<br />

7.5.1 Description of Indicators<br />

‣ POWER indicator<br />

LED indicator Description How to deal with<br />

Light is off or<br />

the green light<br />

flashes<br />

The supply power is<br />

abnormal<br />

Check if the supply power is in the valid range<br />

The green<br />

light keeps on<br />

The supply power is<br />

normal<br />

No resolution is required<br />

‣ RUN indicator<br />

LED indicator Description How to deal with<br />

The green<br />

light is on.<br />

Light is off<br />

PLC is running<br />

PLC is in stop status<br />

No resolution is required<br />

Make PLC run through RUN/STOP switch or<br />

WPLSoft<br />

‣ ERROR indicator<br />

LED indicator Description How to deal with<br />

Light is off PLC is normal No resolution is required<br />

7-23