17.03.2014 Views

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

Error code Description Action<br />

C40B<br />

C40C<br />

C40D<br />

C40E<br />

C40F<br />

C41B<br />

C41C<br />

C41D<br />

C41F<br />

C430<br />

C440<br />

C441<br />

C442<br />

C443<br />

C4EE<br />

C4FF<br />

MC / MCR does not begin from N0 or discontinuously<br />

MC / MCR corresponding value N is different<br />

Use I / P incorrectly<br />

IRET doesn’t follow by the last FEND instruction<br />

SRET doesn’t follow by the last FEND instruction<br />

PLC program and data in parameters have not been<br />

initialized<br />

Invalid RUN/STOP instruction to extension module<br />

The number of input/output points of I/O extension unit is<br />

larger than the specified limit<br />

Number of extension modules exceeds the range<br />

Failing to write data into memory<br />

Initializing parallel interface error<br />

Hardware error in high-speed counter<br />

Hardware error in high-speed comparator<br />

Hardware error in MCU pulse output<br />

No response from extension unit<br />

No END command in the program<br />

Invalid instruction (no such instruction existing)<br />

A circuit error occurs<br />

if a combination of<br />

instructions is<br />

incorrectly specified.<br />

Select programming<br />

mode and correct the<br />

identified error<br />

6.3 Error Detection Devices<br />

Error Check<br />

Devices<br />

Description Drop Latch STOP RUN RUN STOP<br />

M1067 Program execution error flag None Reset Latch<br />

M1068 Execution error latch flag None Latch Latch<br />

D1067 Algorithm error code None Reset Latch<br />

D1068 Step value of algorithm errors None Latch Latch<br />

Device D1067<br />

Error Code<br />

0E18<br />

0E19<br />

0E1A<br />

0E1B<br />

Description<br />

BCD conversion error<br />

Division error (divisor=0)<br />

Floating point exceeds the usage range<br />

The value of square root is negative<br />