<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

6.1 Common Problems and Solutions<br />

The following tables list some common problems and troubleshooting procedures for the PLC system<br />

in the event of faulty operation.<br />

System <strong>Operation</strong><br />

Symptom<br />

Troubleshooting and Corrective Actions<br />

All LEDs are OFF 1. Check the power supply wiring.<br />

2. Check If the power supplied to the PLC control units is in the range of<br />

the rating.<br />

3. Be sure to check the fluctuation in the power supply.<br />

4. Disconnect the power supply wiring to the other devices if the power<br />

supplied to the PLC control unit is shared with them.<br />

If the LEDs on the PLC control unit turn ON at this moment, the<br />

capacity of the power supply is not enough to control other devices<br />

as well. Prepare another power supply for other devices or increase<br />

the capacity of the power supply.<br />

ERROR LED is<br />

flashing<br />

5. If the POWER LED still does not light up when the power is on after<br />

the above corrective actions, the PLC should be sent back to the<br />

dealer or the distributor whom you purchased the product from.<br />

1. If the ERROR LED is flashing, the problem may be an invalid<br />

commands, communication error, invalid operation, or missing<br />

instructions, error indication is given by self-checking function and<br />

corresponding error code and error step are stored in special<br />

registers. The corresponding error codes can be read from the<br />

WPLSoft or HPP. Error codes and error steps are stored in the<br />

following special registers.<br />

Error code: D1004<br />

Error step: D1137<br />

2. If the connections between the PLC are failed and the LED will flash<br />

rapidly, this indicates the DC24V power supply is down and please<br />

check for possible DC24V overload.<br />

3. The LED will be steady if the program loop execution time is over the<br />

preset time (set in D1000), check the programs or the WDT (Watch<br />

Dog Timer). If the LED remains steady, download user program<br />

again and then power up to see if the LED will be OFF. If not, please<br />

check if there is any noise interference or any foreign object in the<br />

PLC.<br />