<strong>DVP</strong>-<strong>ES2</strong><strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

6. Restrictions on diverging sequence: Please refer to section 5.5 for examples<br />

a) Max. 8 step points could be used for single divergence sequence.<br />

b) Max. 16 step points could be used for the convergence of multiple diverted sequences.<br />

c) Users can assign a step in the sequence to jump to any step in another sequence.<br />

7. Reset step points and disable outputs<br />

a) Use the ZRST instruction to reset (turn off) a specified step sequence..<br />

b) Set ON the flag M1034 to disable Y outputs.<br />

8. Latched step:<br />

The ON/OFF status of the latched step will be memorized when the power of the PLC is<br />

switched off. When the PLC is powered up again, PLC will resume the status before power-off<br />

and executes from the interrupted point. Please be aware of the area for the latched steps.<br />

9. Special auxiliary relays and special registers: For more details please refer to 5.6 IST<br />

Instruction.<br />

Device<br />

Description<br />

M1040<br />

M1041<br />

M1042<br />

M1043<br />

M1044<br />

M1045<br />

M1046<br />

M1047<br />

D1040<br />

D1041<br />

D1042<br />

D1043<br />

D1044<br />

D1045<br />

D1046<br />

D1047<br />

Disabling step transition.<br />

Step transition start. Flag for IST instruction.<br />

Enabling pulse operation. Flag for IST instruction.<br />

Zero return completed. Flag for IST instruction.<br />

Zero point condition. Flag for IST instruction.<br />

Disabling “all output reset” function. Flag for IST instruction.<br />

Indicating STL status. M1046 = ON when any step is ON<br />

Enabling STL monitoring<br />

No. of the 1st step point which is ON.<br />

No. of the 2nd step point which is ON<br />

No. of the 3rd step point which is ON.<br />

No. of the 4th step point which is ON<br />

No. of the 5th step point which is ON.<br />

No. of the 6th step point which is ON<br />

No. of the 7th step point which is ON.<br />

No. of the 8th step point which is ON<br />

5-10