<strong>DVP</strong>-<strong>ES2</strong><strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

STL diagram. However, there are restrictions on some of the instructions. Care should be taken<br />

when using the instructions listed in the table below.<br />

Basic Instructions Applicable in a Step<br />

LD/LDI/LDP/LDF<br />

Basic instruction<br />

AND/ANI/ANDP/ANDF ANB/ORB<br />

OR/ORI/ORP/ORF MPS/MRD/MPP<br />

Step point<br />

INV/OUT/SET/RST<br />

MC/MCR<br />

Primary step point/ General step point Yes Yes No<br />

Diverging step<br />

point/<br />

Converging<br />

General output<br />

Step point transfer<br />

Yes<br />

Yes<br />

Yes<br />

Yes<br />

No<br />

No<br />

step point<br />

1. DO NOT use MC/MCR instruction in the step.<br />

2. DO NOT use STL instruction in a general subroutine or interruption subroutine.<br />

3. CJ instruction can be used in STL instruction, however this is not recommended because the<br />

actions will thus become more complicated.<br />

4. Position of MPS/MRD/MPP instruction:<br />

Ladder diagram:<br />

Instruction code: Explanation:<br />

STL Sn MPS/MRD/MPP instruction<br />

LD X0<br />

LD X0<br />

Sn<br />

MPS<br />

cannot be used directly on<br />

X0 X1<br />

MPS<br />

S<br />

Y1<br />

the new bus. You have to<br />

AND X1<br />

X2<br />

BUS MRD<br />

M0 OUT Y1 execute LD or LDI<br />

X3<br />

MRD<br />

instruction first before<br />

MPP<br />

Y2 AND X2 applying MPS/MRD/MPP.<br />

OUT M0<br />

MPP<br />

AND X3<br />

OUT Y2<br />

Other Points to Note:<br />

1. The instruction used for transferring the step (SET S□ or OUT S□) are suggested to be<br />

executed after all the relevant outputs and actions in the current step are completed.<br />

The execution results by the PLC are the same. However, if there are many conditions or<br />

actions in S10, it is recommended to modify the diagram in the left into the diagram in the right,<br />

which executes SET S20 after all actions are completed. The sequence will be more<br />

understandable and clear with this modification.<br />

5-8