2.9 S Relay<br />

Initial step relay<br />

Zero return step relay<br />

Latched step relay<br />

General purpose step relay<br />

Alarm step relay<br />

Starting instruction in Sequential Function Chart (SFC).<br />

S0~S9, total 10 points.<br />

Returns to zero point when using IST instruction in program. Zero<br />

return step relays not used for IST instruction can be used as<br />

general step relays.<br />

S10~S19, total 10 ponits.<br />

In sequential function chart (SFC), latched step relay will be saved<br />

when power loss after running. The state of power on after power<br />

loss will be the same as the sate before power loss.<br />

S20 ~ S127, total 108 points.<br />

General relays in sequential function chart (SFC). They will be<br />

cleared when power loss after running.<br />

S128 ~ S911, total 784 points.<br />

Used with alarm driving instruction API 46 ANS as an alarm<br />

contact for recording the alarm messages or eliminating external<br />

malfunctions.<br />

S912 ~ S1023, total 112 points.<br />

2.10 T (Timer)<br />

The units of the timer are 1ms, 10ms and 100ms and the counting method is counting up. When<br />

the present value in the timer equals the set value, the associated output coil will be ON. The set<br />

value should be a K value in decimal and can be specified by the content of data register D.<br />

The actual set time in the timer = timer resolution× set value<br />

Ex: If set value is K200 and timer resolution is 10ms, the actual set time in timer will be 10ms*200 =<br />

2000ms = 2 sec.<br />

General Timer<br />

The timer executes once when the program reaches END instruction. When TMR instruction is<br />

executed, the timer coil will be ON when the current value reaches its preset value.<br />

When X0 = ON, TMR instruction is driven. When current value achieves K100, the assocailte timer<br />

contact T0 is ON to drive Y0. If X0 = OFFor the power is off, the current value in T0 will be cleared<br />

as 0 and output Y0 driven by contact T0 will be OFF.<br />

X0<br />

TMR T0 K100<br />

T0<br />

Y0<br />

10 sec<br />

X0<br />

T0<br />

Y0<br />

present<br />

value<br />

K100<br />

2-30