<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

Exception response:<br />

The PLC is expected to return a normal response after receiving command messages from the master<br />

device. The following table depicts the conditions that either a no response or an error response is<br />

replied to the master device.<br />

1. The PLC did not receive a valid message due to a communication error; thus the PLC has no<br />

response. The master device will eventually process a timeout condition.<br />

2. The PLC receives a valid message without a communication error, but cannot accommodate it,<br />

an exception response will return to the master device. In the exception response, the most<br />

significant bit of the original command code is set to 1, and an exception code explaining the<br />

condition that caused the exception is returned.<br />

An example of exception response of command code 01H and exception 02H:<br />

Sent message:<br />

Field Name ASCII Hex<br />

STX : 3A<br />

Slave Address 01 30 31<br />

Command code 01 30 31<br />

Starting Address Hi 04 30 34<br />

Starting Address Lo 00 30 30<br />

Number of Points Hi 00 30 30<br />

Number of Points Lo 10 31 30<br />

Error Check (LRC) EA 45 41<br />

END CR LF 0D 0A<br />

Feedback message:<br />

Field Name ASCII Hex<br />

STX : 3A<br />

Slave Address 01 30 31<br />

Function 81 38 31<br />

Exception Code 02 30 32<br />

Error Check (LRC) 7C 37 43<br />

END CR LF 0D 0A<br />

4-6