<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

Available setting for command code:<br />

CMD(Hex) Explanation Device<br />

01 (01 H) Read status of contact S, Y, M, T, C<br />

02 (02 H) Read status of contact S, X, Y, M,T, C<br />

03 (03 H) Read content of register T, C, D<br />

05 (05 H) Force ON/OFF single contact S, Y, M, T, C<br />

06 (06 H) Set content of single register T, C, D<br />

15 (0F H) Force ON/OFF multiple contacts S, Y, M, T, C<br />

16 (10 H) Set content of multiple registers T, C, D<br />

17 (11 H) Retrieve information of Slave None<br />

23 (17 H)<br />

Simultaneous data read/write in a<br />

polling of EASY PLC LINK<br />

None<br />

Example: Read devices T20~T27 (address: H0614~H61B) from Slave ID#01(station number)<br />

PC→PLC<br />

“: 01 03 06 14 00 08 DA CR LF”<br />

Sent massage:<br />

Field name ASCII Hex<br />

STX : 3A<br />

Slave Address 01 30 31<br />

Command code 03 30 33<br />

Starting Address High 06 30 36<br />

Starting Address Low 14 31 34<br />

Number of Points High 00 30 30<br />

Number of Points Low 08 30 38<br />

LRC checksum DA 44 41<br />

END CR LF 0D 0A<br />

PLC→PC<br />

“: 01 03 10 00 01 00 02 00 03 00 04 00 05 00 06 00 07 00 08 C8 CR LF”<br />

Responded massage:<br />

Field name ASCII Hex<br />

STX : 3A<br />

Slave Address 01 30 31<br />

Command code 03 30 33<br />

4-4