3. Instruction Set<br />

EI<br />

M1002<br />

MOV<br />

K100<br />

D1131<br />

MOV<br />

K200<br />

D1340<br />

MOV K300 D1343<br />

MOV<br />

K600<br />

D1348<br />

SET<br />

M1534<br />

DMOV K0 D1030<br />

DMOV K0 C243<br />

M0<br />

DCNT C243 K9999<br />

DHSCS<br />

K50000<br />

C243<br />

I010<br />

DCLLM C243 K50000 K100000 Y0<br />

FEND<br />

I010<br />

M1000<br />

INC<br />

D0<br />

IRET<br />

END<br />

2. Assume the first execution results are as below:<br />

Frequency<br />

100KHz<br />

C243 =K50000<br />

Y0 stops output<br />

D1340<br />

Time<br />

Pulse number<br />

D1343<br />

D1348<br />

6s<br />

Specified number of output pulses: 50,000<br />

Actual number of output pulses (D1030, D1031) = K50,600<br />

3. Observe the results of the first execution:<br />

a) The actual output number 50,600 – specified output number 50,000 = 600<br />

b) 600 x (1/100Hz) = 6s (idle time)<br />

c) 3 seconds are too long. Therefore, increase the percentage value (D1131) to K101.<br />

4. Obatin the results of the second execution:<br />

3-443