<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong> <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

4. D can only designate Y0 (Direction signal output: Y1) or Y2 (Direction signal output: Y3). The<br />

direction signal output will be OFF only when the drive contact of the instruction is OFF, i.e.<br />

completion of pulse output will not reset Y1 or Y3.<br />

5. D1340 and D1352 stores the start/end frequencies of CH0 and CH1. Min. 6Hz, default:<br />

100Hz.<br />

6. D1343 and D1353 stores the ramp up/down time of CH0 and CH1. If the ramp up/down time<br />

is shorter than 20ms, PLC will operate in 20ms. Dafault: 100ms.<br />

7. Ramp-down time of CH0 and CH1 can be particularlily specified by the setting of (M1534,<br />

D1348) and (M1535, D1349). When M1534 / M1535 is ON, ramp-down time of CH0 and CH1<br />

is set by D1348 and D1349.<br />

8. D1131 and D1132 are the output/input ratio(%) of the close loop control in CH0 and CH1. K1<br />

refers to 1 output pulse out of 100 feedback pulses; K200 refers to 200 output pulses out of<br />

the 100 feedback pulses. In general percentage equation, the value set in D1131 and D1132<br />

represents numerators (output pulses, available range: K1 ~ K10,000) and the denominator<br />

(the input feedbacks) is fixed as K100 (System defined).<br />

9. M1305 and M1306 can reverse the direction of CH0, CH1 pulse output. For example, when<br />

direction signal output (Y1/Y3) is OFF, pulse output will operate in positive direction. If<br />

M1305/M1306 is set ON before the execution of this instruction, the pulse output will be<br />

reversed as negative output direction.<br />

10. When S 1 designates input points X with interrupt pointers, D1244 / D1255 can be applied for<br />

setting the idle time as limited pulse number, in case the interrupt is not properly triggered.<br />

11. DCLLM instruction supports Alignment Mark and Mask function. Please refer to PLSR<br />

instruction for details.<br />

Close Loop Explanations:<br />

1. Function: Immediately stop the high-speed pulse output according to the number of<br />

feedback pulses or external interruption signals.<br />

2. Timing diagram:<br />