3. Instruction Set<br />

8. For pulse output with ramp-up/down section, if only 1 axis is specified with pulse output<br />

number, i.e. another axis is 0, the pulse output will only be performed on the axis with output<br />

pulse number. However, if the output pulse number is less than 20 in any of the 2 axes, the<br />

ramp-up/down section will be disabled and pulse output will be executed with the frequency<br />

not higher than 3kHz.<br />

9. There is no limitation on the number of times for using the instruction. However, assume CH0<br />

or CH1 pulse output is in use, the X/Y axis synchronized output will not be performed.<br />

10. M1029 will be ON when 2-axis synchronized pulse output is completed.<br />

Program Example:<br />

1. Draw a rhombus as the figure below.<br />

Y<br />

(0,0)<br />

X<br />

(-27000,-27000)<br />

(27000,-27000)<br />

(0,-55000)<br />

2. Steps:<br />

a) Set the four coordinates (0,0), (-27000, -27000), (0, -55000), (27000, -27000) (as the figure<br />

above). Calculate the relative coordinates of the four points and obtain (-27000, -27000),<br />

(27000, -28000), (27000, 27000), and (-27000, 27000). Place them in the 32-bit registers<br />

(D200, D202), (D204, D206), (D208, D210), (D212, D214).<br />

b) Design instructions as follows.<br />

c) RUN the PLC. Set ON M0 to start the 2-axis line drawing.<br />

3-425