17.03.2014 Views

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong> <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

2. Operand D occupies 8 consecutive word registers. The function of each device is as below:<br />

No. Content Range Format Note<br />

D + 0~1 Zenith 0 ~ 90 Float Horizontal=0<br />

D + 2~3 Azimuth 0 ~ 360 Float North point=0<br />

D + 4~5 Incidence 0 ~ 90 Float<br />

D + 6 Converted DA value of Zenith 0 ~ 2000 Word 1LSB = 0.045<br />

degree<br />

D + 7 Converted DA value of Azimuth 0 ~ 2000 Word 1LSB = 0.18<br />

degree<br />

3. The execution time of SPA instruction costs up to 50ms, therefore we suggest users to<br />

execute this instruction with an interval not less than 1 sec, preventing the instruction from<br />

taking too much PLC operation time.<br />

4. Definition of Zenith: 0° and 45°.<br />

0° 45°<br />

5. Definition of Azimuth:<br />

N<br />

0°<br />

270°<br />

90°<br />

180°<br />

6. The correct time of the local longitude: If we suppose that it is AM8:00:00 in Taipei, and the<br />

longitude is 121.55 degrees east, then the correct time of the local longitude in Taipei should<br />

be AM8:06:12. Please refer to API168 DTM instruction (parameter k11) for more explanation.<br />

3-404