3. Instruction Set<br />

Points to note:<br />

1. There are two methods to correct built-in RTC:<br />

• Correcting by API167 TWR instruction<br />

Please refer to explanation of instruction TWR (API 167)<br />

• Setting by peripheral device<br />

Using WPLSoft / ISPSoft (Ladder editor)<br />

2. Display 4-digit year data:<br />

• D1319 only stores the 2-digit year in A.D. If 4-digit year data is required, please insert the<br />

following instruction at the start of program.<br />

M1002<br />

SET M1016 Display 4-digit year data<br />

• The original 2-digit year will be switched to a 4-digit year, i.e. the 2-digit year will pluses<br />

2,000. If users need to write in new time in 4-digit year display mode, only a 2-digit year<br />

data is applicable (0 ~ 99, indicating year 2000 ~ 2099). For example, 00 = year 2000, 50<br />

= year 2050 and 99 = year 2099.<br />

• Flags and special registers for RTC<br />

Device Content Function<br />

M1016 Year display<br />

mode of RTC<br />

OFF: D1319 stores 2-digit year data in A.D.<br />

ON: D1319 stores 2-digit year data in A.D + 2000<br />

M1017 ±30 seconds<br />

correction on<br />

RTC<br />

Correction takes place when M1017 goes from OFF to<br />

ON (Second data in 0 ~ 29: reset to 0. Second data in<br />

30 ~ 59: minute data pluses 1, second data resets)<br />

Device Content Range<br />

D1313 Second 0-59<br />

D1314 Minute 0-59<br />

D1315 Hour 0-23<br />

D1316 Day 1-31<br />

D1317 Month 1-12<br />

D1318 Day (Mon. ~ Sun.) 1-7<br />

D1319 Year 0-99 (two digit year data)<br />