2. Registers for setting ramp up/down time and start/end frequency:<br />

• Output Y0:<br />

Ramp-up<br />

slope<br />

Sample time<br />

of ramp-up<br />

Pulse output frequency<br />

Start freq.<br />

Y0(D1340)<br />

Min: 6Hz<br />

End freq.<br />

Y0 (D1340)<br />

Min: 6Hz<br />

Current<br />

position<br />

Ramp up time<br />

Default: 100ms<br />

Y0(D1343)<br />

Ramp down time<br />

Default: 100ms<br />

Y0(D1343)<br />

Target position<br />

• This instruction can be used many times in user program, but only one instruction will be<br />

activated at a time. For example, if Y0 is currently activated, other instructions use Y0<br />

won’t be executed. Therefore, instructions first activated will be first executed.<br />

• After activating the instruction, all parameters cannot be modified unless instruction is<br />

OFF.<br />

• For associated special flags and special registers, please refer to Points to note of<br />

DDRVI instruction.<br />

3-376