3. Instruction Set<br />

API Mnemonic Operands Function<br />

157 D PLSV<br />

Adjustable Speed Pulse<br />

Output<br />

Controllers<br />

<strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SA2</strong> <strong>SX2</strong><br />

SE<br />

Type Bit Devices Word Devices Program Steps<br />

OP X Y M S K H KnX KnY KnM KnS T C D E F PLSV: 7 steps<br />

S * * * * * * * * * * * DPLSV: 13 steps<br />

D 1 *<br />

D 2 * * *<br />

PULSE 16-bit 32-bit<br />

<strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SA2</strong><br />

<strong>SA2</strong><br />

<strong>SA2</strong><br />

<strong>SX2</strong> <strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SX2</strong> <strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong><br />

SE SE SE <strong>SX2</strong><br />

Operands:<br />

S: Pulse output frequency D 1 : Pulse output device (Y0, Y2) D 2 : Direction signal output<br />

Explanations:<br />

1. The instruction only supports the pulse output type: Pulse + Direction.<br />

2. S is the designated pulse output frequency. Available range: -100,000Hz ~ +100,000 Hz. “+/-”<br />

signs indicate forward/reverse output direction. The frequency can be changed during pulse<br />

output. However, if the specified output direction is diferent from the current output direction, the<br />

instruction will stop for 1 scan cycle then restart with the changed frequency.<br />

3. D 1 is the pulse output device. It can designate CH0(Y0) and CH1(Y2).<br />

4. D 2 is the direction signal output device. It can designate CH0(Y1) and CH1(Y3).<br />

5. The operation of D 2 corresponds to the “+” or “-“ of S. When S is “+”, D 2 will be OFF; when S is “-“,<br />

D 2 will be ON.<br />

6. M1305 and M1306 can change the output direction of CH0/CH1 set in D 2 . When S is “-“, D 2 will<br />

be ON, however, if M1305/M1306 is set ON before instruction executes, D 2 will be OFF during<br />

execution of instruction.<br />

7. PLSV instruction does not support settings for ramp up or ramp down. If ramp up/down process is<br />

required, please use API 67 RAMP instruction.<br />

8. If the drive contact turns off during pulse output process, pulse output will stop immediately.<br />

Program Example:<br />

When M10 = ON, Y0 will output pulses at 20kHz. Y1 = OFF indicates forward direction.<br />

M10<br />

DPLSV K20000 Y0 Y1<br />

3-369