<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

4. When D is specified as Y0, its direction signal output is Y1; when D is specified as Y2, its direction<br />

signal output is Y3.<br />

5. When pulse output reaches zero point, pulse output execution completed flag M1029 (CH0),<br />

M1102 (CH1) is ON and the register indicating current position is reset to 0.<br />

6. When DZRN instruction executes, external interrupt I400/I401(X4)) or I600/I601(X6) in program<br />

will be disabled until DZRN instruction is completed. Also. If left limit switch (X5 / X7) is enabled<br />

during instruction execution, external interrupt I500501(X5) or I700/I701(X7) will be disabled as<br />

well.<br />

7. Zero point selection: the default position of zero point is on the left of DOG switch (the input point<br />

On→Off) (as mode 1 shows). If the user needs to change the zero point to the right of DOG switch,<br />

set ON M1106(CH0) or M1107(CH1) before DZRN instruction executes. (The function supports<br />

<strong>ES2</strong>/<strong>EX2</strong> series, V1.20 or above.)<br />

8. Start the pulse-clearing function of the output. When DOG leaves DOG switch and is going to stop,<br />

it will output another pulse (the width of On is about 20ms). When the pulse is On→Off, there will<br />

be a completed flag output. Please refer to state 4 for the timing diagram of this function. (The<br />

function supports <strong>ES2</strong>/<strong>EX2</strong> series, V1.20 or above.)<br />

9. When D1312 is not set to be 0, and M1308=Off, the function of seeking Z phase is started. When<br />

D1312 is a positive value (the maximum value is 10), it indicates that the search for Z-phase signal<br />

is toward the positive direction. When D1312 is a negative value (the minimum value is -10), it<br />

indicates that the search for Z-phase signal is toward the negative direction. For example, if D1312<br />

is k-2, it means that DOG stops immediately after DOG leaves DOG switch and searches in the<br />

negative direction for second Z-phase signal (the fixed right-edge trigger) with JOG frequency.<br />

Please refer to state 5 for the timing diagram of this function. (The function supports <strong>ES2</strong>/<strong>EX2</strong><br />

series of V1.20 or above, and <strong>SS2</strong>/<strong>SX2</strong> series of V1.20 or above.)<br />

10. When D1312 is not set to be 0 and M1308=On, the function of outputting the designated number<br />

of pulses is started. When Dd1312 is a positive value (the maximum value is 30000), it indicates<br />

that the pulses are output in the positive direction. When D1312 is a negative value (the minimum<br />

value is -30000), it indicates that the pulses are output in the negative direction. For example, if<br />

D1312 is k-100, it means that DOG stops immediately after DOG leaves DOG switch and another<br />

100 pulses will be output in the negative direction with JOG frequency. Please refer to state 6 for<br />

the timing diagram of this function. (The function supports <strong>ES2</strong>/<strong>EX2</strong> series of V1.40 or above, and<br />

<strong>SS2</strong>/<strong>SX2</strong> series of V1.20 or above.)<br />

11. Timing Diagram:<br />

State 1: Current position at right side of DOG switch, pulse output in reverse, limit switch disabled.<br />

3-364