3. Instruction Set<br />

PLC VFD-B,PLC transmits: “01 10 2000 0002 04 1770 0012 EE 0C”<br />

VFD-BPLC, PLC receives: ”01 10 2000 0002 4A08”<br />

Registers for data to be sent (sending messages)<br />

Register Data Descriptions<br />

D1256 Low byte 01 H Address<br />

D1257 Low byte 10 H Function<br />

D1258 Low byte<br />

D1259 Low byte<br />

D1260 Low byte<br />

D1261 Low byte<br />

20 H<br />

00 H<br />

00 H<br />

02 H<br />

Data Address<br />

Number of Register<br />

D1262 Low byte 04 H Byte Count<br />

D1263 Low byte<br />

D1264 Low byte<br />

D1265 Low byte<br />

D1266 Low byte<br />

17 H<br />

70 H<br />

00 H<br />

12 H<br />

Data<br />

content 1<br />

Data<br />

content 2<br />

D1262 Low byte EE H CRC CHK Low<br />

D1263 Low byte 0C H CRC CHK High<br />

Registers for received data (responding messages)<br />

The content of D50: H1770 (K6000)<br />

The content of D51: H0012 (K18)<br />

Register Data Descriptions<br />

D1070 Low byte 01 H Address<br />

D1071 Low byte 10 H Function<br />

D1072 Low byte<br />

D1073 Low byte<br />

D1074 Low byte<br />

D1075 Low byte<br />

20 H<br />

00 H<br />

00 H<br />

02 H<br />

Data Address<br />

Number of Register<br />

D1076 Low byte 4A H CRC CHK Low<br />

D1077 Low byte 08 H CRC CHK High<br />

Program example 12: COM1 (RS-232) / COM3 (RS-485), Function Code H10<br />

1. Function code K16 (H10): Write in multiple Word devices. Up to 16 Words can be written. For<br />

PLC COM2 ASCII mode, only 8 words can be written.<br />

2. PLC COM1/COM3 will not process the received data<br />

3. Take the connection between PLC COM3 and VFD-B for example, the tables below explain<br />

the status when PLC COM3 writes multiple Words in VFD-B. (M1320 = OFF, ASCII mode)<br />

(M1320 = ON, RTU mode)<br />

• If PLC applies COM1 for communication, the below program can be usable by changing:<br />

1. D1109→D1036: communication protocol<br />

3-357