3. Instruction Set<br />

4. Take the connection between PLC1 (PLC COM2) and PLC2 (PLC COM1) for example, the<br />

tables below explain the status when PLC1 force ON/OFF Y0~Y17 of PLC2.<br />

Set value: K4Y0=1234H<br />

Device Status Device Status Device Status Device Status<br />

Y0 OFF Y1 OFF Y2 ON Y3 OFF<br />

Y4 ON Y5 ON Y6 OFF Y7 OFF<br />

Y10 OFF Y11 ON Y12 OFF Y13 OFF<br />

Y14 ON Y15 OFF Y16 OFF Y17 OFF<br />

M1002<br />

MOV<br />

H87<br />

D1120<br />

Set communication protocol as 9600, 8, E, 1<br />

SET<br />

M1120<br />

Retain communication protocol<br />

MOV<br />

K100<br />

D1129<br />

Set receiving timeout as 100ms<br />

X0<br />

RST<br />

SET<br />

M1143<br />

M1122<br />

M1143 = OFF<br />

ASCII mode<br />

Sending request<br />

SET<br />

M1143<br />

M1143 = ON<br />

RTU mode<br />

X0<br />

MODRW<br />

K1<br />

K15<br />

H0500 D0 K16<br />

Receiving completed<br />

M1127<br />

Processing received data<br />

Data length(bit)<br />

Data storing register<br />

Data address: H0500<br />

Function code: K15<br />

Write in multiple bit devices<br />

Connection device<br />

address: K1<br />

ASCII mode: The received data is stored in D1070~D1085 in ASCII format.<br />

RTU mode: The received data is stored in D1070~ D1085 in Hex format.<br />

RST<br />

M1127<br />

Reset M1127<br />

ASCII mode (M1143 = OFF)<br />

When X0 = ON, MODRW instruction executes the function specified by Function Code H0F.<br />

PLC1 PLC2, PLC sends: “ 01 0F 0500 0010 02 3412 93 ”<br />

PLC2 PLC1, PLC receives: “ 01 0F 0500 0010 DB ”<br />

Registers for data to be sent (sending messages)<br />

Register Data Descriptions<br />

D1256 下 ‘0’ 30 H ADR 1<br />

D1256 上 ‘1’ 31 H ADR 0<br />

Device address: ADR (1,0)<br />

D1257 下 ‘0’ 30 H CMD 1<br />

D1257 上 ‘F’ 46 H CMD 0<br />

Control parameter: CMD (1,0)<br />

D1258 下 ‘0’ 30 H<br />

D1258 上 ‘5’ 35 H<br />

D1259 下 ‘0’ 30 H<br />

Data Address<br />

D1259 上 ‘0’ 30 H<br />

3-351