3. Instruction Set<br />

Register Data Descriptions<br />

D5<br />

0000 H<br />

PLC converts ASCII codes in 2105 H and stores the converted<br />

data automatically.<br />

RTU mode (COM3: M1320 = ON COM1: M1139 = ON):<br />

When X0 = ON, MODRW instruction executes the function specified by Function Code 03<br />

PLC VFD-B, PLC sends: ” 01 03 2100 0006 CF F4”<br />

VFD-B PLC, PLC receives: “01 03 0C 0000 0503 0BB8 0BB8 0000 012D 8E C5”<br />

Registers for received data (responding messages)<br />

Register Data Descriptions<br />

D0<br />

D1<br />

D2<br />

D3<br />

D4<br />

D5<br />

0000 H<br />

0503 H<br />

0BB8 H<br />

0BB8 H<br />

0136 H<br />

012D H<br />

PLC converts data in 2100 H and stores the converted data<br />

automatically.<br />

PLC converts data in 2101 H and stores the converted data<br />

automatically.<br />

PLC converts data in 2102 H and stores the converted data<br />

automatically.<br />

PLC converts data in 2103 H and stores the converted data<br />

automatically.<br />

PLC converts data in 2104 H and stores the converted data<br />

automatically.<br />

PLC converts data in 2105 H and stores the converted data<br />

automatically.<br />

Program example 5: COM2(RS-485), Function Code H05<br />

1. Function code K5(H05): Force ON/OFF bit device<br />

2. PLC1 connects to PLC2: (M1143 = OFF, ASCII mode), (M1143 = ON, RTU Mode)<br />

3. n = 1 indicates Force ON (set FF00H) and n = 0 indicates Force OFF (set 0000H)<br />

4. For ASCII or RTU mode, PLC COM2 stores the data to be sent in D1256~D1295 and stores<br />

the received data in D1070~D1085<br />

5. Take the connection between PLC1 (PLC COM2) and PLC2 (PLC COM1) for example, the<br />

tables below explain the status when PLC1 Force ON PLC2 Y0.<br />