17.03.2014 Views

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

M1002<br />

MOV H86 D1120<br />

Set up communication protocol as<br />

9600, 7, E, 1<br />

SET<br />

M1120<br />

Retain communication protocol<br />

MOV K100 D1129<br />

Set up communication time-out: 100ms<br />

X0<br />

M1129<br />

SET<br />

M1122<br />

Sending request<br />

X0<br />

RSTEF K1 K0<br />

Receiving completed<br />

M1127<br />

Processing received data<br />

Communication instruction setting:<br />

Device address: 1 K0: Reserved<br />

RST<br />

M1127<br />

Reset M1127.<br />

PLC VFD, PLC sends: “:01 06 2002 0002 D5 ”<br />

VFD PLC, PLC sends: “:01 06 2002 0002 D5 ”<br />

Data to be sent (sending messages):<br />

Data<br />

‘0’ 30 H ADR 1<br />

‘1’ 31 H ADR 0<br />

‘0’ 30 H CMD 1<br />

‘6’ 36 H CMD 0<br />

‘2’ 32 H<br />

‘0’ 30 H<br />

‘0’ 30 H<br />

Data address<br />

‘2’ 32 H<br />

‘0’ 30 H<br />

‘0’ 30 H<br />

‘0’ 30 H<br />

Data contents<br />

‘2’ 32 H<br />

‘D’ 44 H LRC CHK 1<br />

‘5’ 35 H LRC CHK 0<br />

Descriptions<br />

AC drive address : ADR (1,0)<br />

Command code: CMD (1,0)<br />

Error checksum: LRC CHK (0,1)<br />

3-288