17.03.2014 Views

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

Feedback Explanation Data storage<br />

N format. D1076 low<br />

A Retrieved status content. The content of ”ABCD” differs D1077 low<br />

B according to value 00~03 set in NN. 00 ~ 03 indicates<br />

D1078 low<br />

C frequency, current and operation mode respectively.<br />

D1079 low<br />

D Please refer to the explanations below for details.<br />

D1080 low<br />

Nn = “00” Frequency command = ABC.D (Hz)<br />

Nn = “01” Output frequency = ABC.D (Hz)<br />

Nn = “02” Output current = ABC.D (A)<br />

PLC will automatically convert the ASCII characters ”ABCD” into D1050. For<br />

example, ”ABCD” = “0600”, PLC will convert ABCD into K0600 (0258 H) and store<br />

it in the special register D1050.<br />

Nn = “03” <strong>Operation</strong> command<br />

‘A’ = ‘0’ Stop, ‘5’ JOG (forward)<br />

‘1’ Forward operation ‘6’ JOG (reverse)<br />

‘2’ Stop, ‘7’ JOG (reverse)<br />

‘3’ Reverse operation ‘8’ Abnormal<br />

‘4’ JOG (forward),<br />

PLC will automatically convert the ASCII character in ”A” into D1051.<br />

For example, ”A” = “3”, PLC will convert A into K3 and store it in the<br />

special register D1051.<br />

‘B’ = b7 b6 b5 b4 Frequency reference source<br />

0 0 0 0 Digital keypad<br />

0 0 0 1 1 st Step Speed<br />

0 0 1 0 2 nd Step Speed<br />

0 0 1 1 3 rd Step Speed<br />

0 1 0 0 4 th Step Speed<br />

0 1 0 1 5 th Step Speed<br />

0 1 1 0 6 th Step Speed<br />

0 1 1 1 7 th Step Speed<br />

1 0 0 0 JOG frequency<br />

1 0 0 1 Analog input frequency command<br />

1 0 1 0 RS-485 communication interface<br />

1 0 1 1 Up/Down control<br />

b3 = 0 Non-DC braking stop 1 DC braking stop<br />

b2 = 0 Non-DC braking start 1 DC braking start<br />

b1 = 0 Forward 1 Reverse<br />

b0 = 0 Stop 1 Run<br />

PLC will store bit status of ”B” in special auxiliary relay M1168 (b0) ~<br />

M1175 (b7).<br />

“CD” = “00” No error “10” OcA<br />

“01” oc “11” Ocd<br />

“02” ov “12” Ocn<br />

“03” oH “13” GFF<br />

“04” oL “14” Lv<br />

“05” oL1 “15” Lv1<br />

“06” EF “16” cF2<br />

“07” cF1 “17” bb<br />

“08” cF3 “18” oL2<br />

“09” HPF “19”<br />

PLC will automatically convert the ASCII characters in ”CD” into D1052.<br />

For example, ”CD” = “16”, PLC will convert CD into K16 and store it in<br />

the special register D10512<br />

8. M1177 = ON, other Delta VFDs are supoported<br />

3-284