3. Instruction Set<br />

API Mnemonic Operands Function<br />

105 RDST Read VFD Status<br />

Controllers<br />

<strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SA2</strong> <strong>SX2</strong><br />

SE<br />

Type Bit Devices Word devices Program Steps<br />

OP X Y M S K H KnX KnY KnM KnS T C D E F RDST: 5 steps<br />

S * * *<br />

n * * *<br />

Operands:<br />

S: Device address n: Status content to be retrieved<br />

PULSE 16-bit 32-bit<br />

<strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SA2</strong><br />

<strong>SA2</strong><br />

<strong>SA2</strong><br />

<strong>SX2</strong> <strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SX2</strong> <strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong><br />

SE SE SE <strong>SX2</strong><br />

Explanations:<br />

1. M1177 = OFF (Default), RDST instruction supports COM2(RS-485).<br />

2. M1177= ON, RDST instruction supports COM2(RS-485), COM3(RS-485).<br />

3. M1177 has to be set up in advance for selecting the target model of VFD. When M1177 = OFF<br />

(Default), RDST instruction supports Delta’s VFD-A inverter. When M1177 = ON, the<br />

instruction supports other models of VFD inverters, e.g. VFD-B, VFD.<br />

4. There is no limitation on the times of using RDST instruction, however only one instruction can<br />

be executed on single COM port at a time<br />

5. Rising-edge contacts (LDP, ANDP, ORP) and falling-edge contacts (LDF, ANDF, ORF) can<br />

not be used with RDST instructions. Otherwise, the data in receiving registers will be<br />

incorrect.<br />

6. For detailed information of associated flags and special registers, please refer to RS<br />

instruction.<br />

7. M1177 = OFF, only VFD-A is supported<br />

a) Range of S: K0 ~ K31<br />

b) Range of n: K0 ~ K3<br />

c) n: Status content to be retrieved<br />

n=0, frequency<br />

n=1, output frequency<br />

n=2, output current<br />

n=3, <strong>Operation</strong> command<br />

d) The feedback data consists of 11 bytes (refer to VFD-A user manual), and will be stored<br />

in low bytes of D1070 ~ D1080.<br />

”Q, S, B, Uu, Nn, ABCD”<br />

Feedback Explanation Data storage<br />

Q Header of question string: ’Q’ (51H). D1070 low<br />

S Checksum: 03H. D0171 low<br />

B Acknowledge back. Correct: 06H, Error: 07H. D1072 low<br />

U Communication address (range: 00~31). Displayed in<br />

D1073 low<br />

U ASCII format.<br />

D1074 low<br />

N Status content to be retrieved (00 ~ 03). Displayed in ASCII D1075 low<br />