<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

Registers for data to be sent (sending messages)<br />

Register Data Descriptions<br />

D1089 low ‘C’ 43 H Header of control string<br />

D1090 low ‘♥’ 03 H Checksum<br />

D1091 low ‘☺’ 01 H<br />

Command acknowledgement<br />

(communication mode)<br />

D1092 low ‘0’ 30 H<br />

D1093 low ‘0’ 30 H<br />

D1094 low ‘0’ 30 H<br />

Communication address<br />

D1095 low ‘1’ 31 H<br />

D1096 low ‘0’ 30 H<br />

D1097 low ‘5’ 35 H<br />

D1098 low ‘0’ 30 H<br />

<strong>Operation</strong> command<br />

D1099 low ‘0’ 30 H<br />

Registers for received data (responding messages)<br />

Register DATA Explanation<br />

D1070 low ‘C’ 43 H Header of control string<br />

D1071 low ‘♥’ 03 H Checksum<br />

D1072 low ‘♠’ 06 H<br />

Acknowledge back. (Check feedback data)<br />

(correct: 06H, Error: 07 H)<br />

D1073 low ‘0’ 30 H<br />

D1074 low ‘0’ 30 H<br />

D1075 low ‘0’ 30 H<br />

Communication address<br />

D1076 low ‘1’ 31 H<br />

D1077 low ‘0’ 30 H<br />

D1078 low ‘5’ 35 H<br />

D1079 low ‘0’ 30 H<br />

<strong>Operation</strong> command<br />

D1080 low ‘0’ 30 H<br />

2. M1177 = ON, other Delta VFDs are supoported<br />

a) S 1 = Address of VFD-A. Range of S 1 : K0 ~ K255, when S 1 is specified as K0, PLC will<br />

broadcast to all connected VFDs.<br />

b) S 2 = Running frequency of VFD. Please refer to manuals of specific VFD. In STOP<br />

instruction, operand S 2 is reserved.<br />

c) n = <strong>Operation</strong> mode.<br />

• In FWD instruction: n = 0 Forward mode; n = 1 Forward JOG. Other values<br />

will be regarded as normal forward mode.<br />

• In REV instruction: n = 0 Reverse mode; n = 1 Reverse JOG. Other values<br />

will be regarded as normal reverse mode<br />