3. Instruction Set<br />

5. If rising-edge (LDP, ANDP, ORP) or falling-edge (LDF, ANDF, ORF) contacts are used before<br />

FWD, REV, STOP instructions, sending request flags M1122 (COM2) / M1316 (COM3) has to<br />

be enabled in advance for obtaining correct operation.<br />

6. For detailed information of associated flags and special registers, please refer to RS<br />

instruction.<br />

7. M1177 = OFF, only Delta VFD-A is supported and the definition of each operand is:<br />

a) S 1 = Address of VFD-A. Range of S 1 : K0 ~ K31<br />

b) S 2 = <strong>Operation</strong> frequency of VFD. Set value for VFD A-type inverter: K0 ~ K4,000<br />

(0.0Hz ~ 400.0Hz).<br />

c) n = Communication mode. Range: K1 ~ K2. n = 1: communicate with VFD at designated<br />

address. n = 2: communicate with all connected VFDs. .<br />

d) The feedback data from the peripheral equipment will be stored in D1070 ~ D1080 After<br />

data receiving is completed, PLC will check if all data are correct automatically. If there<br />

is an error, M1142 will be ON. When n = 2, PLC will not receive any data.<br />

Program Example: COM2 (RS-485)<br />

1. Communication between PLC and VFD-A series inverter. Retry for communication time-out<br />

and data receiving error.<br />

M1002<br />

MOV H0073 D1120<br />

Set up communication protocol as<br />

4800, 8, O, 1<br />

SET<br />

M1120<br />

Retain communication protocol<br />

X0<br />

M1129<br />

M1142<br />

MOV K100 D1129 Set up communication time-out: 100ms<br />

SET M1122 Sending request<br />

Retry when receiving time-out occurs<br />

Retry when data receiving error<br />

X0<br />

FWD K0 K500 K1<br />

Receiving completed<br />

M1127<br />

Processing received data<br />

Communication instruction setting:<br />

Device address: 0<br />

Frequency: 500Hz<br />

K1: communicate with the designated VFD<br />

The received data is stored in low byte<br />

of D1070 ~ D1080 in ASCII format.<br />

RST<br />

M1127<br />

Reset M1127<br />

PLC VFD-A, PLC sends: “C ♥ ☺ 0001 0500 ”<br />

VFD-A PLC, PLC receives: “C ♥ ♠ 0001 0500 ”<br />

3-279