17.03.2014 Views

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

DVP-ES2-EX2-SS2-SA2-SX2-Operation Manual

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

Registers for received data (responding messages)<br />

Register Data Descriptions<br />

D1070 low byte ‘0’ 30 H ADR 1<br />

D1070 high byte ‘1’ 31 H ADR 0<br />

D1071 low byte ‘0’ 30 H CMD 1<br />

D1071 high byte ‘3’ 33 H CMD 0<br />

D1072 low byte ‘0’ 30 H<br />

D1072 high byte ‘C’ 43 H<br />

Number of data (count by byte)<br />

D1073 low byte ‘0’ 30 H<br />

0100 H<br />

D1073 high byte ‘1’ 31 H Content of address PLC automatically converts<br />

D1074 low byte ‘0’ 30 H 2101 H<br />

ASCII codes and store the<br />

D1074 high byte ‘0’ 30 H<br />

converted value in D1050<br />

D1075 low byte ‘1’ 31 H<br />

1766 H<br />

D1075 high byte ‘7’ 37 H Content of address PLC automatically converts<br />

D1076 low byte ‘6’ 36 H 2102 H<br />

ASCII codes and store the<br />

D1076 high byte ‘6’ 36 H<br />

converted value in D1051<br />

D1077 low byte ‘0’ 30 H<br />

0000 H<br />

D1077 high byte ‘0’ 30 H Content of address PLC automatically converts<br />

D1078 low byte ‘0’ 30 H 2103 H<br />

ASCII codes and store the<br />

D1078 high byte ‘0’ 30 H<br />

converted value in D1052<br />

D1079 low byte ‘0’ 30 H<br />

0000 H<br />

D1079 high byte ‘0’ 30 H Content of address PLC automatically converts<br />

D1080 low byte ‘0’ 30 H 2104 H<br />

ASCII codes and store the<br />

D1080 high byte ‘0’ 30 H<br />

converted value in D1053<br />

D1081 low byte ‘0’ 30 H<br />

0136 H<br />

D1081 high byte ‘1’ 31 H Content of address PLC automatically converts<br />

D1082 low byte ‘3’ 33 H 2105 H<br />

ASCII codes and store the<br />

D1082 high byte ‘6’ 36 H<br />

converted value in D1054<br />

D1083 low byte ‘0’ 30 H<br />

0000 H<br />

D1083 high byte ‘0’ 30 H Content of address PLC automatically converts<br />

D1084 low byte ‘0’ 30 H 2106 H<br />

ASCII codes and store the<br />

D1084 high byte ‘0’ 30 H<br />

converted value in D1055<br />

D1085 low byte ‘3’ 33 H LRC CHK 1<br />

D1085 high byte ‘B’ 42 H LRC CHK 0<br />