<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

API Mnemonic Operands Function<br />

93 ANDF Falling-edge series connection<br />

Controllers<br />

<strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SA2</strong><br />

SE<br />

<strong>SX2</strong><br />

Type Bit Devices Word devices Program Steps<br />

OP X Y M S K H KnX KnY KnM KnS T C D E F ANDF: 3 steps<br />

S * * * * * *<br />

Operands:<br />

S: falling edge contact to be connected in series<br />

PULSE 16-bit 32-bit<br />

<strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SA2</strong><br />

<strong>SA2</strong><br />

<strong>SA2</strong><br />

<strong>SX2</strong> <strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SX2</strong> <strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong><br />

SE SE SE <strong>SX2</strong><br />

Explanations:<br />

ANDF instruction is used in the series connection of the falling-edge contact.<br />

Program Example:<br />

Ladder Diagram:<br />

X0<br />

X1<br />

Y1<br />

Instruction Code:<br />

<strong>Operation</strong>:<br />

LD X0 ; Load NO contact of X0<br />

ANDF X1 ; X1 falling-edge contact in series connection<br />

OUT Y1 ; Drive Y1 coil<br />