3. Instruction Set<br />

Example 2: Block diagram of application on AC motor drive (S 3 +4 = 0)<br />

Speed instruction (S)<br />

S+MV<br />

AC motor<br />

drive<br />

Acceleration/deceleration<br />

instruction (SV)<br />

PID<br />

Acceleration/deceleration<br />

output (MV)<br />

Actual acceleration/<br />

deceleration speed<br />

(PV = S - P)<br />

Speed<br />

detection<br />

device (P)<br />

Example 3: Block diagram of application on temperature control (S 3 +4 = 1)<br />

Temperature instruction (SV)<br />

PID<br />

Heating (MV)<br />

Heater<br />

Actual temperature<br />

(PV)<br />

Temperature<br />

detection<br />

device<br />

Example 4: PID parameters adjustment<br />

Assume that the transfer function of the controlled device G(S) in a control system is a first-order<br />

function b<br />

G()<br />

s = (model of general motors), SV = 1, and sampling time (T S ) = 10ms. Suggested<br />

s + a<br />

steps for adjusting the parameters are as follows:<br />

Step1:<br />

Set K I<br />

and K D<br />

as 0, and K P<br />

as 5, 10, 20, 40. Record the SV and PV respectively and the results are<br />

as the figure below.<br />

1.5<br />

K P=40<br />

K P=20<br />

K P=10<br />

SV=1<br />

1<br />

0.5<br />

K =5 P<br />

0 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1<br />

Time (sec)<br />