3. Instruction Set<br />

Special register<br />

D1070~D1085<br />

Function<br />

Feedback data (ASCII) of Modbus communication. When PLC’s<br />

RS-485 communication instruction receives feedback signals, the data<br />

will be saved in the registers D1070~D1085 and then converted into<br />

Hex in other registers.<br />

RS instruction is not supported.<br />

D1089~D1099<br />

Sent data of Modbus communication. When PLC’s RS-485<br />

communication instruction (MODRD) sends out data, the data will be<br />

stored in D1089~D1099. Users can check the sent data in these<br />

registers.<br />

RS instruction is not supported<br />

D1120<br />

D1121<br />

D1122<br />

D1123<br />

D1124<br />

D1125<br />

D1126<br />

D1129<br />

D1130<br />

COM2 (RS-485) communication protocol. Refer to the following table in<br />

point 4 for protocol setting.<br />

COM1 (RS-232) and COM2 (RS-485) PLC communication address<br />

when PLC is slave.<br />

COM2 (RS-485) Residual number of words of transmitting data.<br />

COM2 (RS-485) Residual number of words of the receiving data.<br />

COM2 (RS-485) Definition of start character (STX) Refer to the<br />

following table in point 3 for the setting.<br />

Supported communication instruction: RS<br />

COM2 (RS-485) Definition of first ending character (ETX1) Refer to the<br />

following table in point 3 for the setting.<br />

Supported communication instruction: RS<br />

COM2 (RS-485) Definition of second ending character (ETX2) Refer to<br />

the following table in point 3 for the setting.<br />

Supported communication instruction: RS<br />

COM2 (RS-485) Communication time-out setting (unit: ms). If users set<br />

up time-out value in D1129 and the data receiving time exceeds the<br />

time-out value, M1129 will be set ON and the error code K1 will be<br />

stored in D1130. M1129 has to be reset manually when time-out status<br />

is cleared.<br />

COM2 (RS-485) Error code returning from Modbus. RS instruction is<br />

not included.<br />

Supported communication instructions: MODRD / MODWR / FWD /<br />

REV / STOP / RDST / RSTEF / MODRW<br />

3-215