<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

Flag Function Action<br />

M1314<br />

M1315<br />

COM1 Data receiving completed. When data receiving of<br />

communication instructions is completed, M1314 will be ON. Users<br />

can process the received data when M1314 is ON. When data<br />

processing is completed, M1314 has to be reset by users.<br />

Supported communication instructions: RS / MODRW<br />

COM1 receiving error. M1315 will be set ON when errors occur and<br />

the error code will be stored in D1250.<br />

Supported communication instructions: RS / MODRW<br />

System<br />

sets<br />

and user<br />

resets<br />

System<br />

sets and<br />

user<br />

resets<br />

Special register<br />

D1036<br />

D1167<br />

D1121<br />

D1249<br />

D1250<br />

Function<br />

COM1 (RS-232) communication protocol. Refer to the following table in<br />

point 4 for protocol setting.<br />

The specific end word to be detected for RS instruction to execute an<br />

interruption request (I140) on COM1 (RS-232).<br />

Supported communication instructions: RS<br />

COM1 (RS-232) and COM2 (RS-485) communication address.<br />

COM1 (RS-232) Communication time-out setting (unit: ms). If users set<br />

up time-out value in D1249 and the data receiving time exceeds the<br />

time-out value, M1315 will be set ON and the error code K1 will be<br />

stored in D1250. M1315 has to be reset manually when time-out status<br />

is cleared.<br />

COM1 (RS-232) communication error code.<br />

Supported communication instructions: MODRW<br />

2. PLC COM2 RS-485: Associated flags (Auxiliary relays) and special registers (Special D) for<br />

communication instructions RS / MODRD / MODWR / FWD / REV / STOP / RDST / RSTEF /<br />

MODRW.<br />

Flag Function Action<br />

M1120<br />

Retain communication settings. Communication settings will be<br />

reset (changed) according to the content in D1120 after every scan<br />

cycle. Users can set ON M1120 if the communication protocol<br />

requires to be retained. When M1120 = ON, communication<br />

settings will not be reset (changed) when communication<br />

instructions are being processed, even if the content in D1120 is<br />

changed.<br />

User<br />

sets/resets<br />

3-212