3. Instruction Set<br />

Registers for received data (VFD-B responds with messages)<br />

Register Data Explanation<br />

D120 low ‘: ’ 3A H STX<br />

D120 high ‘0’ 30 H ADR 1<br />

D121 low ‘1’ 31 H ADR 0<br />

D121 high ‘0’ 30 H CMD 1<br />

D122 low ‘3’ 33 H CMD 0<br />

D122 high ‘0’ 30 H<br />

D123 low ‘C’ 43 H<br />

Number of data (counted by byte)<br />

D123 high ‘0’ 30 H<br />

D124 low ‘1’ 31 H<br />

D124 high ‘0’ 30 H<br />

Content of address 2101 H<br />

D125 low ‘0’ 30 H<br />

D125 high ‘1’ 31 H<br />

D126 low ‘7’ 37 H<br />

D126 high ‘6’ 36 H<br />

Content of address 2102 H<br />

D127 low ‘6’ 36 H<br />

D127 high ‘0’ 30 H<br />

D128 low ‘0’ 30 H<br />

D128 high ‘0’ 30 H<br />

Content of address 2103 H<br />

D129 low ‘0’ 30 H<br />

D129 high ‘0’ 30 H<br />

D130 low ‘0’ 30 H<br />

D130 high ‘0’ 30 H<br />

Content of address 2104 H<br />

D131 low ‘0’ 30 H<br />

D131 high ‘0’ 30 H<br />

D132 low ‘1’ 31 H<br />

D132 high ‘3’ 33 H<br />

Content of address 2105 H<br />

D133 low ‘6’ 36 H<br />

D133 high ‘0’ 30 H<br />

D134 low ‘0’ 30 H<br />

D134 high ‘0’ 30 H<br />

Content of address 2106 H<br />

D135 low ‘0’ 30 H<br />

D135 high ‘3’ 33 H LRC CHK 1<br />

D136 low ‘B’ 42 H LRC CHK 0<br />

D136 high CR D H<br />

D137 low LF A H<br />

END<br />

3. The status of Delta VFD series inverters can also be accessed by handy instruction API 105<br />

RDST instruction through COM2/COM3 on PLC.<br />