3. Instruction Set<br />

182. Please use transistor output for Y20 ~ Y23. Every pin 1, 2, 4, 8 shall be connected to a diode<br />

(0.1A/50V) in series before connecting to the input terminals on PLC.<br />

Wiring diagram of DIP switch:<br />

DIP switches for<br />

BCD wiring<br />

10 0 10 1 10 2 10 3<br />

Must connect to a<br />

diode (1N4148) in<br />

series<br />

0V +24V<br />

1 2 4 8 1 2 4 8<br />

S/S X20 X21 X22 X23 X24 X25 X26 X27<br />

The first group<br />

The second group<br />

C<br />

Y20<br />

Y21<br />

Y22<br />

Y23<br />

PLC<br />

0 1 2 3<br />

10 10 10 10<br />

Points to note:<br />

When the terminals to be scanned are relay outputs, the following program methods can be applied:<br />

183. When X30 = ON, DSW instruction will be executed. When X30 goes OFF, M10 remains ON<br />

until the current scan cycle of output terminals is completed..<br />

184. If the drive contact X30 uses button switch, M10 turns off only when the current scan cycle on<br />

outputs is completed, so that a correct value from DIP switch can be read. In addition, the<br />

continuous scan cycle on outputs will be performed only when the drive contact is pressed and<br />

held. Applying this method can reduce the driving frequency of relay outputs so as to extend to<br />

life-span of relays.<br />

X30<br />

M10<br />

M1029<br />

SET M10<br />

DSW X20 Y20 D20 K2<br />

RST M10<br />

3-189