<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

111. M10~ M13 = ON when the current value of C10 falls between lower and upper bounds.<br />

Lower-bound value Upper- bound value Current value of C10 Output<br />

D100= 40 D101 = 100 40≦C10≦100 M10 = ON<br />

D102 = 120 D103 = 210 120≦C10≦210 M11 = ON<br />

D104 = 140 D105 = 170 140≦C10≦170 M12 = ON<br />

D106 = 150 D107 = 390 150≦C10≦390 M13 = ON<br />

112. If the lower bound value is bigger than upper bound value, when C10 140, M12 =<br />

ON.<br />

Lower- bound value Upper- bound value Current value of C10 Output<br />

D100 = 40 D101 = 100 40≦C10≦100 M10 = ON<br />

D102 = 120 D103 = 210 120≦C10≦210 M11 = ON<br />

D104 = 140 D105 = 60 60≦C10≦140 M12 = OFF<br />

D106 = 150 D107 = 390 150≦C10≦390 M13 = ON<br />

M10<br />

M11<br />

40 100<br />

120 210<br />

M12<br />

M13<br />

60 140<br />

150 390<br />

0<br />

200<br />

400<br />

3-162