3. Instruction Set<br />

Explanations:<br />

When M0 is triggered, Y0 executes pulse output. When external interrupt is detected on X4<br />

after 50,000 pulses, pulse output will perform ramp down process for 10,000 pulses and then<br />

stop. M1108 will be ON. If no interrupt is detected on X4, Y0 pulse output will stop after<br />

1,000,000 pulses are completed.<br />

Interrupt triggered between 0 ~ 50,000 pulses will be invalid, i.e. no ramp-down process will be<br />

performed before 50,000 pulses are achieved.<br />

Points to note:<br />

1. When Mark function is executed with Mask function, PLC will check the validity of Mask<br />

range first, then ramp-down stop pulses of Mark function. If the above set values exceed<br />

the proper range, PLC will automatically modify the set values after the instruction is<br />

executed.<br />

2. When PLSR or positioning instructions with ramp-up/down section are enabled, the user<br />

can check the pulses of ramp-up section in DD1127 and pulses of ramp-down section in<br />

DD1133.<br />

3. Users can perform single speed positioning when ramp-up/down time setting is not<br />

specified.<br />

3-151