3. Instruction Set<br />

API Mnemonic Operands Function<br />

59 D PLSR Pulse Ramp<br />

Controllers<br />

<strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SA2</strong><br />

SE<br />

<strong>SX2</strong><br />

Type Bit Devices Word devices Program Steps<br />

OP X Y M S K H KnX KnY KnM KnS T C D E F PLSR: 9 steps<br />

S 1 * * * * * * * * * * * DPLSR: 17 steps<br />

S 2 * * * * * * * * * * *<br />

S 3 * * * * * * * * * * *<br />

D *<br />

PULSE 16-bit 32-bit<br />

<strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SA2</strong><br />

<strong>SA2</strong><br />

<strong>SA2</strong><br />

<strong>SX2</strong> <strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong> <strong>SX2</strong> <strong>ES2</strong>/<strong>EX2</strong> <strong>SS2</strong><br />

SE SE SE <strong>SX2</strong><br />

Operands:<br />

S 1 : Maximum frequency (Hz) S 2 : Number of pulses S 3 : Ramp up/down time (ms)<br />

D: Pulse output device (Y0, Y1, Y2 and Y3 are available) (<strong>DVP</strong>-SE does not support Y1 and Y3.)<br />

Explanations:<br />

52. PLSR instruction performs a frequency ramp up/down process when positioning. Speed ramp<br />

up process is activated between static status to the target speed. Pulse output persists in<br />

target speed before getting close to target position. When target position is near, speed ramp<br />

down process executes, and pulse output stops when target position is achieved.<br />

53. Set range of S 1 pulse output frequency:<br />

Range of S 1 pulse output frequency:<br />

Output Y0, Y2 Y1, Y3<br />

<strong>SS2</strong>: 6~10,000Hz<br />

Output 16-bit<br />

6~10,000Hz<br />

<strong>ES2</strong>/<strong>EX2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE: 6~32,767Hz<br />

frequency:<br />

<strong>SS2</strong>: 6~10,000Hz<br />

32-bit<br />

6~10,000Hz<br />

<strong>ES2</strong>/<strong>EX2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE: 0~100,000Hz<br />

If frequency smaller than 6Hz is specified, PLC will output 6Hz.<br />

If frequency bigger than max frequency is specified, PLC will output with max frequency.<br />

54. When output device is specified with Y0, Y2, the start/end frequency of Y0 is set by D1340 and<br />

start/end frequency of Y2 is set by D1352.<br />

55. When output device is specified with Y1, Y3, the start/end frequency is 0Hz.<br />

56. When D1220/D1221 = K1 or K2, positive/negative sign of S 2 denotes pulse output direction.<br />

57. PLSR instruction supports two modes of pulse output as below list.<br />

Mode<br />

D1220<br />

D1221<br />

Output K0 K1 K0 K1<br />

Y0 Pulse Pulse<br />

Y1 Pulse Dir<br />

Y2 Pulse Pulse<br />

3-145