3. Instruction Set<br />

46. When M1113 = ON, the unit of Y2 output pulse is 10μs, when M1113 = OFF, the unit is 100μs.<br />

(It is not applicable to <strong>DVP</strong>-SE.)<br />

47. When M1113 = ON, the unit of Y2 output pulse is 100μs, when M1113 = OFF, the unit is 1ms.<br />

(It is only applicable to <strong>DVP</strong>-SE.)<br />

48. When M1071 = ON, the unit of Y3 output pulse is 100μs, when M1071 = OFF, the unit is 1ms.<br />

49. When M1116 is ON, M1112 and M1113 do not work. The time unit of the pulse output through<br />

Y0 and Y2 is 1μs. <strong>DVP</strong>-<strong>ES2</strong> version 3.00/<strong>SS2</strong> version 2.80/<strong>SA2</strong> version 2.60/SE version<br />

2.60/<strong>SX2</strong> version 2.40 support this function.<br />

50. When M1117 is ON, M1070 and M1071 do not work. The time unit of the pulse output through<br />

Y1 and Y3 is 10μs. <strong>DVP</strong>-<strong>ES2</strong> version 3.00/<strong>SS2</strong> version 2.80/<strong>SA2</strong> version 2.60/SE version<br />

2.60/<strong>SX2</strong> version 2.40 support this function.<br />

51. If M1116 for <strong>DVP</strong>-<strong>SS2</strong> is enabled, the minimum pulse output width should be larger than 20.<br />

Otherwise, due to the limitations on the hardware bandwidth of Y0 and Y2, the output result is<br />

not the correct time width.<br />

Program Example:<br />

When X0 = ON, Y1 output the pulse as shown<br />

opposite. When X0 = OFF, output Y1 turns OFF.<br />

X0<br />

PWM K1000 K2000 Y1<br />

t=1000ms<br />

Output Y1<br />

T=2000ms<br />

Note:<br />

1. Flag description:<br />

M1070: Switching clock pulse of Y1 for PWM instruction (ON:100 us, OFF: 1ms)<br />

M1071: Switching clock pulse of Y3 for PWM instruction (ON:100 us, OFF: 1ms)<br />

M1112 Switching clock pulse of Y0 for PWM instruction (ON:10 us/100µs for SE; OFF:<br />

100 us/1ms for SE)<br />

M1113 Switching clock pulse of Y2 for PWM instruction (ON:10 us, OFF: 100 us)<br />

M1116 If M1116 is ON, the time unit of the pulse output through Y0 and Y2 is 1μs.<br />

M1112 and M1113 do not work.<br />

M1117 If M1117 is ON, the time unit of the pulse output through Y1 and Y3 is 10μs.<br />

M1070 and M1071 do not work.<br />

2. Special D registers description:<br />

D1030 PV of Y0 pulse output (Low word)<br />

D1031<br />

PV of Y0 pulse output (High word)<br />