<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

25. Four pulse output modes: (They are not applicable to <strong>DVP</strong>-SE.)<br />

Mode<br />

D1220<br />

D1221<br />

Output K0 K1 K2 K3 K0 K1 K2 K3 #<br />

Y0 Pulse Pulse A CW<br />

Y1 Pulse Dir B Pulse<br />

Y2 Pulse Pulse A CCW<br />

Y3 Pulse Dir B Pulse<br />

Pulse: Pulse A: A phase pulse CW: clockwise<br />

Dir: Direction B: B phase pulse CCW: Counter-clockwise<br />

Note # : When D1220 is specified as K3, D1221 is invalid.<br />

26. Four pulse output modes: (They are only applicable to <strong>DVP</strong>-SE.)<br />

Mode<br />

D1220<br />

D1221<br />

Output K0 K1 K3 # K0 K1 K3 #<br />

Y0 Pulse Pulse CW<br />

Y1 Pulse Dir Pulse<br />

Y2 Pulse Pulse CCW<br />

Y3 Pulse Dir Pulse<br />

27. Pulse output flags:<br />

Output device Y0 Y1 Y2 Y3<br />

Completed Flag M1029 M1030 M1102 M1103<br />

Immediately pause M1078 M1079 M1104 M1105<br />

0.01~10Hz output M1190 M1191 M1192 M1193<br />

a) M1029 = ON after Y0/Y1 (D1220=K1, pulse/Dir) output is completed.<br />

M1102 = ON after Y2/Y3 (D1221=K1, pulse/Dir) output is completed.<br />

M1029 = ON after the Y0/Y2 (D1220 = K3, CW/CCW) output is completed.<br />

b) The execution completed flag M1029, M1030, M1102, and M1103 should be manually<br />

reset by users after pulse output is completed.<br />

c) When PLSY / DPLSY instruction is OFF, the pulse output completed flags will all be reset.<br />

d) When M1190~M1192 = ON, the available output range for PLSY Y0~Y3 is 0.01~10Hz.<br />

28. While the PLSY instruction is being executed, the output will not be affected if S 2 is changed.<br />

To change the pulse output number, stop the PLSY instruction, then change the pulse number.<br />

29. S 1 can be changed during program execution and the change will take effects until the<br />

modified PLSY instruction is being executed.<br />

30. The ratio of OFF time and ON time of the pulse output is 1:1.<br />

31. If operand S 1 , S 2 use index F, only 16-bit instruction is available.<br />