1. PLC Concepts<br />

Example 2 - Start First latched circuit<br />

When X1 (START) = ON and X2 (STOP) = OFF, Y1 will be ON<br />

and latched. If X2 is turned ON, Y1 remains ON. This is a Start<br />

First circuit because START button has the control priority than<br />

STOP<br />

X1<br />

Y1<br />

X2<br />

Y1<br />

Example 3 - Latched circuit of SET and RST<br />

The diagram opposite are latched circuits consist of RST and<br />

SET instructions.<br />

Stop first<br />

X1<br />

X2<br />

SET<br />

RST<br />

Y1<br />

Y1<br />

In PLC processing principle, the instruction close to the end of<br />

the program determines the final output status of Y1. Therefore,<br />

if both X1 and X2 are ON, RST which is lower than SET forms a<br />

Stop First circuit while SET which is lower than RST forms a<br />

Start First circuit.<br />

Start first<br />

X2<br />

X1<br />

RST<br />

SET<br />

Y1<br />

Y1<br />

Example 4 - Power down latched circuit<br />

The auxiliary relay M512 is a latched relay. Once X1 is ON, Y1<br />

retains its status before power down and resumes after power<br />

up.<br />

X1<br />

X2<br />

SET<br />

RST<br />

M512<br />

M512<br />

M512<br />

Y1<br />

Example 5 - Conditional Control<br />

X1<br />

X3<br />

Y1<br />

X1<br />

Y1<br />

X3<br />

X2<br />

Y2<br />

X4<br />

Y1<br />

Y2<br />

X2<br />

X4<br />

Y1<br />

Y2<br />

Because NO contact Y1 is connected to the circuit of Y2 output, Y1 becomes one of the conditions<br />

for enabling Y2, i.e. for turning on Y2, Y1 has to be ON<br />

1-17