3. Instruction Set<br />

DHSZ instruction. Also, when DHSCS uses I070 or I080, comparators B3 and B4 are no<br />

longer available for DHSZ instruction. If comparators are used repeatedly, the syntax<br />

error will be detected on the instruction behind.<br />

‣ For <strong>DVP</strong>-SE, if DHSZ instruction uses hardware comparators, two hardware<br />

comparators are used. DHSCS instruction and DHSCR instruction can not use the same<br />

hardware comparators.<br />

Program Example 1: (Applying Hardware High Speed Counter)<br />

6. When D is specified as Y0, then Y0~Y2 will be occupied automatically.<br />

7. When DHSZ is executed, the instruction compares the current value in C246 with the<br />

upper/lower bound (1500/2000) of the comparison zone, and Y0~Y2 will be ON according to<br />

the comparison result.<br />

M1000<br />

DCNT C246 K20000<br />

Y0<br />

Y1<br />

Y2<br />

DHSZ K1500 K2000 C246 Y0<br />

When current value of C246 < K1500, Y0=On<br />

When K1500 < current value of C246 < K2000, Y1=On<br />

When current value of C246 > K2000, Y2=On<br />

Program Example 2: (Applying DHSZ instruction for performing ramp down operation)<br />

8. C251 is AB-phase high speed counter. When X10 = ON, DHSZ compare the present value<br />

with K2000. Present value≦<br />

K2000, Y10 = ON.<br />

9. When X10 = OFF, Y10~Y12 are reset.<br />

X10<br />

RST C251<br />

M1000<br />

X10<br />

ZRST Y10 Y12<br />

DCNT C251 K10000<br />

DHSZ K2000 K2400 C251 Y10<br />

3-133