<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

‣ There are 6 software zone comparators available exclusively for zone compare operation,<br />

hence the limit of 6 comparisons for zone compare does not include the comparisons of<br />

DHSCS and DHSCR.<br />

‣ <strong>SS2</strong>/<strong>SA2</strong>/SE does not support software counter C232.<br />

5. Explanations on hardware comparators for HSZ instruction:<br />

‣ Corresponding table for hardware counters and comparators (It is not applicable to<br />

VEP-SE):<br />

Hardware counter<br />

A group<br />

B group<br />

A1 A2 A3 A4 B1 B2 B3 B4<br />

Counter No. C243, C245~C248, C251,C252 C244, C249, C250, C253, C254<br />

High-speed compare<br />

Set/Reset<br />

Shares 4 hardware<br />

comparators for group A<br />

Shares 4 hardware<br />

comparators for group B<br />

‣ Corresponding table for hardware counters and comparators (It is only applicable to<br />

VEP-SE):<br />

Hardware counter<br />

A group<br />

B group<br />

A1 A2 B1 B2<br />

Counter No. C243, C245~C248, C251,C252 C244<br />

High-speed<br />

compare Set/Reset<br />

Shares 2 hardware comparators<br />

for group A<br />

Shares 2 hardware<br />

comparators for group B<br />

‣ Block diagram of hardware counters and comparators:<br />

Hardware<br />

comparator A x 4<br />

Set /reset A1<br />

I010 A1<br />

Hardware<br />

counter A<br />

Count<br />

value<br />

A<br />

Set /res et<br />

I040<br />

A4<br />

A4<br />

Hardware<br />

comparator B x 4<br />

Set /reset<br />

I050<br />

B1<br />

B1<br />

Hardware<br />

counter B<br />

Count<br />

value<br />

B<br />

Set /reset B4<br />

I080 B4<br />

‣ The two groups can only be used once for each group, occupying 2 comparators. For<br />

example, when DHSZ instruction uses A3 and A4 of group A comparators, only the other<br />

2 comparators (A1, A2) are available for DHSCS and DHSCR instructions.<br />

‣ When DHSCS uses I030 or I040, comparators A3 and A4 are no longer available for<br />