<strong>DVP</strong>-<strong>ES2</strong>/<strong>EX2</strong>/<strong>SS2</strong>/<strong>SA2</strong>/<strong>SX2</strong>/SE <strong>Operation</strong> <strong>Manual</strong> - Programming<br />

‣ If DCNT instruction enables C243 as high speed counter (group A) and DHSC/DHSC<br />

instruction uses C245 as high speed counter (group A) at the same time, PLC takes<br />

C243 as the source counter automatically and no syntax check error will be detected.<br />

‣ Table of settings for the high-speed interrupts of hardware counters and comparators:<br />

(It is not applicable to <strong>DVP</strong>-SE.)<br />

Hardware counter<br />

A group<br />

B group<br />

A1 A2 A3 A4 B1 B2 B3 B4<br />

Counter No. C243, C245~C248, C251,C252 C244, C249, C250, C253, C254<br />

High-speed counter<br />

interrupt<br />

I010 I020 I030 I040 I050 I060 I070 I080<br />

High-speed compare<br />

Set/Reset<br />

Share 4 hardware<br />

comparators for group A<br />

Share 4 hardware<br />

comparators for group B<br />

‣ Table of settings for the high-speed interrupts of hardware counters and comparators:<br />

(It is only applicable to <strong>DVP</strong>-SE.)<br />

Hardware counter<br />

A group<br />

B group<br />

A1 A2 B1 B2<br />

Counter No. C243, C245~C248, C251,C252 C244<br />

High-speed counter<br />

I010 I020 I050 I060<br />

interrupt<br />

Hi-speed compare<br />

Set/Reset<br />

Share 2 hardware<br />

comparators for group A<br />

Share 2 hardware<br />

comparators for group B<br />

‣ Block diagram of hardware counters and comparators:<br />

Hardware<br />

comparator A x 4<br />

Set /res et<br />

I010<br />

A1<br />

A1<br />

Hardware<br />

counter A<br />

Count<br />

value<br />

A<br />

Set /res et<br />

I040<br />

A4<br />

A4<br />

Hardware<br />

comparator B x 4<br />

Set /reset<br />

I050<br />

B1<br />

B1<br />

Hardware<br />

counter B<br />

Count<br />

value<br />

B<br />

Set /reset B4<br />

I080 B4<br />

7. Difference between software and hardware comparators (it is not applicable to <strong>DVP</strong>-SE):<br />